Environmental Monitoring Digitale Eingänge, Digital Inputs, Binary Inputs, Dry Contact Inputs

Environmental Monitoring
 

Environmental Monitoring Digitale Eingänge, Digital Inputs, Binary Inputs, Dry Contact Inputs

 
Terminal Black
 

The binary inputs for bistable sensor connecting. "Dry Contact" means direct connection of zero-potencial contact. The inputs indicates only two statuses - "On"/"Off" ("Open"/"Close") which Poseidon analyses as "Normal" / "Alarm".
The Connector wiring can be found in a manual for individual Poseidon model. (>> The list of Poseidon models )

* Range of measurement: two Statuses: On/Off (Open/Close or Alarm/Normal )
* Maximum wiring length: 50 to 300 meters (see the device model)
* Type of sensor: contact (switching or disconnecting)
* Power supply: no external power supply
* Maximal current: 20 mA
* Distinguishing level: On (stapled contact) = resistance 0Ω to 500Ω.
* Communication cable: pair cable (phone or twisted UTP cable)

* Alarm setting: "Normally Open" or "Normally Closed" - configurable over software
* Sampling period: circa twice a second
* Sensor address: connector provides the address
* Disconnecting sensor detection: No

Dry contact inputs diagramTypical sensors connecting to this interface:

* Open/close door detector
* Detector of flooding and water level
* Smoke, fire or exceeding of dangerous gas concentration level detector
* Movement sensor, output from alarm exchange
* PowerEgg supports detection of 110 to 230V electric voltage

 
 

BellEquip GmbH • Franz Eigl-Straße 8 • 3910 Zwettl • Österreich / Austria • Tel.: +43 (0)2822 33 33 990 • Fax: +43 (0)2822 33 33 995
Internet: www.bellequip.at • E-Mail: info[a]bellequip.at